Siemens SSA-045512: Node2Shell Brotli flaw CVE-2026-111497 (CVSS 3.1 9.8) affects Desigo CC V8 and V9 and Gridscale X; fixes via .NET updates and new Gridscale versions, per Siemens
Siemens ProductCERT advisory SSA-045512 (published 30 Oct 2026, version V1.2 updated 6 Nov 2026) lists Siemens products affected by Node2Shell, CVE-2026-111497, an out-of-bounds write in the Brotli decoder bundled with Node.js that Siemens rates CVSS 3.1 9.8 and CVSS 4.0 9.2.
Siemens says all versions of Desigo CC family V8 and V9 are affected and should install the latest .NET security updates via Windows Update; Gridscale X DSA V5.3 up to before V5.4 should update to V5.4 or later; and Gridscale X PSS®E before V36.8.0 should update to V36.8.0 or later. Siemens added Desigo CC on 4 Nov and the Gridscale X products on 6 Nov. (source: Siemens SSA-045512)
CISA republished the advisory as ICSA-26-316-02 on 12 November 2026, listing the products as deployed worldwide in the critical manufacturing, energy and information technology sectors. (source: CISA ICSA-26-316-02)
Correction (13 Nov 2026): this card said neither Siemens nor CISA reports exploitation. CISA's Known Exploited Vulnerabilities catalog has listed CVE-2026-111497 in the Brotli decoder as exploited since 27 October 2026; Siemens' advisory and CISA's ICS advisory do not report exploitation of Siemens products. (source: CISA Known Exploited Vulnerabilities catalog)
- Product
- Siemens Desigo CC family V8 and V9; Gridscale X DSA; Gridscale X PSS®E
- Versions
- Per Siemens SSA-045512 V1.2 (6 Nov 2026): Desigo CC family V8 and V9: all versions; Gridscale X DSA >= V5.3 < V5.4; Gridscale X PSS®E < V36.8.0.
- CVSS
- (CVSS 3.1) / 9.2 (CVSS 4.0), per Siemens
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CVSS:4.0/AT:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N - Exploited in Australia?
- unknown
- Patch to
- Per Siemens (SSA-045512 V1.2): Desigo CC family V8 and V9: install the latest .NET security updates via Windows Update; Gridscale X DSA: update to V5.4 or later; Gridscale X PSS®E: update to V36.8.0 or later.
- Primary: Siemens ProductCERT — SSA-045512: Node2Shell Vulnerability in Siemens Products (30 Oct 2026, V1.2 6 Nov 2026)
- Vendor: Siemens SSA-045512 remediation table
- CVE: CVE-2026-111497
- Source: CISA ICS advisory ICSA-26-316-02 — Siemens Desigo, Gridscale (12 Nov 2026)
- Source: CISA — Known Exploited Vulnerabilities catalog (JSON feed, catalog version 2026.11.10): CVE-2026-111497 added 27 October 2026