Vulnerability
Published 2026-10-30
Updated 2026-11-13
Verified 2026-11-14

Siemens SSA-443410: Node2Shell flaw CVE-2026-111497 (CVSS 3.1 9.8) affects Industrial Edge Management and device apps; fixes for most, none yet for Common Configurator, per Siemens

Siemens ProductCERT advisory SSA-443410 (published 30 Oct 2026, version V1.1 updated 6 Nov 2026) covers Node2Shell, CVE-2026-111497, a Brotli decoder out-of-bounds write that Siemens rates CVSS 3.1 9.8 and CVSS 4.0 9.2, in Industrial Edge.

Siemens says it is still assessing the impact: Industrial Edge Management (IEM) setups with no Management Applications installed need no action, while setups with Management or Device Applications installed should follow the mitigations until a fix is available. Siemens lists fixed versions for Cloud Connector Configurator, Data Flow Monitoring, Databus Configurator, DataXess Configurator, Edge OPC UA Server Configurator and Flow Creator Configurator, says Industrial Edge Hub and Industrial Edge Management Cloud were fixed on its central cloud service from 29 and 28 October with no user action needed, and says no fix is currently available for Common Configurator on IEM or on Device. (source: Siemens SSA-443410)

CISA republished the advisory as ICSA-26-316-03 on 12 November 2026. (source: CISA ICSA-26-316-03)

Correction (13 Nov 2026): this card said neither Siemens nor CISA reports exploitation. CISA's Known Exploited Vulnerabilities catalog has listed CVE-2026-111497 in the Brotli decoder as exploited since 27 October 2026; Siemens' advisory and CISA's ICS advisory do not report exploitation of Siemens products. (source: CISA Known Exploited Vulnerabilities catalog)

Product
Siemens Industrial Edge Management applications and device applications; Industrial Edge Hub; Industrial Edge Management Cloud
Versions
Per Siemens SSA-443410 V1.1 (6 Nov 2026): Cloud Connector Configurator < V1.24.3; Common Configurator (CC on IEM) and Common Configurator on Device (CC on Edge): all versions; Data Flow Monitoring < V3.0.18; Databus Configurator < V4.0.1; DataXess Configurator < V1.5.7; Edge OPC UA Server Configurator < V2.3.10; Flow Creator Configurator < V1.15.1; Industrial Edge Hub and Industrial Edge Management Cloud: all versions (fixed centrally).
CVSS
(CVSS 3.1) / 9.2 (CVSS 4.0), per Siemens
Exploited in Australia?
unknown
Patch to
Per Siemens (SSA-443410 V1.1): update Cloud Connector Configurator to V1.24.3, Data Flow Monitoring to V3.0.18, Databus Configurator to V4.0.1, DataXess Configurator to V1.5.7, Edge OPC UA Server Configurator to V2.3.10 and Flow Creator Configurator to V1.15.1 or later. Common Configurator on IEM: uninstall all Management Applications and protect the IEM instance with a firewall/WAF until a fix is available; Common Configurator on Device: stop it until a fix is available. Industrial Edge Hub and Industrial Edge Management Cloud: fixed centrally, no user action.

vulnerabilities ot ics