Siemens SSA-242944 and SSA-678870: Node2Shell flaw CVE-2026-111497 (CVSS 3.1 9.8) affects WinCC, TIA Administrator, UMC, Teamcenter, Opcenter and other products; most have no fix yet, per Siemens
Siemens ProductCERT published two advisories on 10 November 2026 (V1.0) on Node2Shell, CVE-2026-111497, the out-of-bounds write in the Brotli decoder bundled with Node.js that Siemens says could allow a remote attacker to cause memory corruption and potentially execute arbitrary code; Siemens rates it CVSS 3.1 9.8 and CVSS 4.0 9.2. SSA-242944 (Siemens Industrial Products) lists COMOS Walkinside, Project Server Web Administration Tool, SIMATIC BRAUMAT and SISTAR (V8.2 Update 1 to before V8.2 Update 5), SIMATIC Profiling Tool, SIMATIC WinCC Companion, WinCC OA V3.20 (before V3.20 P17.1) and V3.21, WinCC Runtime Professional, WinCC Unified (for Industrial Edge, PC Runtime, SIQENCE), WinCC V7/V8, TIA Administrator and User Management Component (UMC) as affected.
Siemens lists fixes only for BRAUMAT and SISTAR (V8.2 Update 5) and WinCC OA V3.20 (P17.1); it says no fix is currently available for the others, and no fix is planned for SIMATIC Profiling Tool. SSA-678870 (Siemens Software Products) lists all versions of HyperLynx, Innexis Architecture Native Acceleration 2026, Insights Hub, Opcenter products, PADS Pro Essentials, PADS Pro Student Edition, PADS Professional, PAVE360 Automotive 2026, Process Preparation X, Simcenter Executable Digital Twin, Simcenter Studio, Teamcenter V2412 to V2606 and Xpedition Designer and Enterprise as affected, with no fix currently available; Siemens says Polarion is not affected. (source: Siemens SSA-242944, SSA-678870)
CISA republished the advisories as ICSA-26-321-03 and ICSA-26-321-04 on 17 November 2026. (source: CISA ICSA-26-321-03, ICSA-26-321-04) CISA's Known Exploited Vulnerabilities catalog has listed CVE-2026-111497 (Google Brotli) since 27 October 2026; the Siemens and CISA ICS advisories do not report exploitation of Siemens products. (source: CISA Known Exploited Vulnerabilities catalog)
- Product
- Siemens SIMATIC WinCC (V7/V8, Runtime Professional, Unified, OA, Companion), TIA Administrator, UMC, BRAUMAT, SISTAR, COMOS Walkinside; Teamcenter, Opcenter, Simcenter, HyperLynx, PADS Pro, Xpedition, Insights Hub and other Siemens software
- Versions
- Per Siemens SSA-242944 V1.0: SIMATIC BRAUMAT and SISTAR >= V8.2 Update 1 < V8.2 Update 5; WinCC OA V3.20 < V3.20 P17.1; all versions of the other listed products. Per SSA-678870 V1.0: all versions of the listed products, including Teamcenter V2412, V2506, V2512 and V2606.
- CVSS
- (CVSS 3.1) / 9.2 (CVSS 4.0), per Siemens
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CVSS:4.0/AT:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N - Exploited in Australia?
- unknown
- Patch to
- Per Siemens: update SIMATIC BRAUMAT and SISTAR to V8.2 Update 5 or later and WinCC OA V3.20 to P17.1 or later. Where no fix is available, Siemens recommends temporarily disabling Brotli compression and decompression at the application or proxy layer if not strictly required; for TIA Administrator (with UMC authentication) and UMC, block requests with Content-Encoding "br" using IIS Request Filtering; for Opcenter and Process Preparation X, mitigate on the IIS reverse proxy (Siemens bulletin PL8869211); for Teamcenter, follow bulletin PL8869204; for HyperLynx, PADS and Xpedition, disable Brotli compression and block it at the network firewall.
- Primary: Siemens ProductCERT — SSA-242944: Node2Shell Vulnerability in Siemens Industrial Products (V1.0, 10 Nov 2026)
- Vendor: Siemens ProductCERT — SSA-678870: Broccoli2Shell Vulnerabilities in Siemens Software Products (V1.0, 10 Nov 2026)
- CVE: CVE-2026-111497
- Source: CISA ICS advisory ICSA-26-321-03 — Siemens Industrial Automation Software Products (17 Nov 2026); see also ICSA-26-321-04
- Source: CISA ICS advisory ICSA-26-321-04 — Siemens Industrial Software Products (17 Nov 2026)